1. The location of the fume hood within the laboratory and the location and method of
introducing supply air to the laboratory is crucial to the safe operation of the hood. The
hood must be located in an area of limited traffic. Supply air must
be introduced into the space opposite from the hood and with minimum
velocity. Perforated duct air outlets are preferred. Standard diffusers are not
acceptable.